https://www.phoenixcontact.com/us/products/2800710
Surge protection device - SYS N4/I 120/240S - 2800710
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://download.phoenixcontact.com)
Indoor/outdoor lightning arrester and TVSS system for 120/240 single/split phase
Product description
Combination lightning arrester and TVSS for 120/240 V single/split phase. Components are housed in an IP66/NEMA 4 cabinet and include phase
indicator lamps.
Key commercial data
Packing unit
1 pc
Custom tariff number
85363090
Country of origin
Germany
Technical data
Dimensions
Height
500 mm
Width
400 mm
Depth
210 mm
Ambient conditions
Degree of protection
IP66 / NEMA 4
Ambient temperature (operation)
-40 °C ... 80 °C
General
Housing material
Steel
Mounting type
Surface/Wall mounting
Surge protection fault message
Remote indicator contact
Protective circuit
IEC test classification
I + II
EN type
T1
2/4/14 Page 1 / 4
https://www.phoenixcontact.com/us/products/2800710
Surge protection device - SYS N4/I 120/240S - 2800710
Technical data
Protective circuit
Nominal voltage UN
< 240 V
Maximum continuous operating voltage UC
275 V AC
Impulse discharge current (10/350) µs, charge
25 As
Impulse discharge current (10/350) µs, peak value limp
50 kA (per mode)
Response time
≤ 25 ns
Follow current quenching capacity If
50 kA
Connection, protective circuit
Connection method
Screw connection
Conductor cross section stranded min.
16 mm²
Conductor cross section stranded max.
35 mm²
Conductor cross section solid min.
10 mm²
Conductor cross section solid max.
50 mm²
Conductor cross section AWG/kcmil min.
6
Conductor cross section AWG/kcmil max
1
Remote indicator contact
Connection method
Screw connection
Conductor cross section stranded min.
0.14 mm²
Conductor cross section stranded max.
1.5 mm²
Conductor cross section solid min.
0.14 mm²
Conductor cross section solid max.
1.5 mm²
Conductor cross section AWG/kcmil min.
28
Conductor cross section AWG/kcmil max
16
NEMA / UL data
UL type
type 2
Nominal discharge current In (without reference direction)
20 kA
Maximum Surge Current per Phase
50 kA
Short-circuit current rating (SCCR)
50 kA
Standards and Regulations
Standards/regulations
rd
UL 1449 3 edition, Sept. 2009
IEC 60643-1
EN 61643-11
CAN/CSA-C22.2 No. 8
2/4/14 Page 2 / 4
https://www.phoenixcontact.com/us/products/2800710
Surge protection device - SYS N4/I 120/240S - 2800710
Classifications
eCl@ss
eCl@ss 4.0
27140201
eCl@ss 4.1
27140201
eCl@ss 5.0
27130801
eCl@ss 5.1
27130801
eCl@ss 6.0
27130805
eCl@ss 7.0
27130805
eCl@ss 8.0
27130805
ETIM
ETIM 3.0
EC000942
ETIM 4.0
EC000941
ETIM 5.0
EC000941
UNSPSC
UNSPSC 6.01
30212010
UNSPSC 7.0901
39121610
UNSPSC 11
39121610
UNSPSC 12.01
39121610
UNSPSC 13.2
39121620
Approvals
Approvals
Approvals
ETLus / cETL / cETLus
Ex Approvals
Approvals submitted
Approval details
ETLus
2/4/14 Page 3 / 4
https://www.phoenixcontact.com/us/products/2800710
Surge protection device - SYS N4/I 120/240S - 2800710
Approvals
cETL
cETLus
Drawings
Circuit diagram
N/GND
L1
L2
© Phoenix Contact 2013 - all rights reserved
http://www.phoenixcontact.com
2/4/14 Page 4 / 4
很抱歉,暂时无法提供与“SYS N4/I 120/240S”相匹配的价格&库存,您可以联系我们找货